Suzhou Yueniao Machinery&Electronics Imp&Exp Co Ltd
| INV SERIES | A300 |



 

 

INV Series inverter supply is the static sine wave one mainly for posts and telecommunications, railway and electric system in which DC power is supplied for AC equipment. The isolating transformer output makes inverter own superstrong overload capacity. This series is applicable for many system such as power equipment, communication system, server and computer network and provides higher-grade elecreic power supply for them. While AC is abnormal or DC is used up, it will automatically switch into DC/AC power supply so as to ensure the safety of the system on higher degree.

Model

INV500VA

INV1KVA

INV2KVA

INV3KVA

INV5KVA

INV10KVA

INV15KVA

INV20KVA

INV30KVA

INV40KVA

Rated power
400W
800W
1600W
2400W
4000W
8000W
12000W
16000W
24000W
32000W
DC Input voltage
24VDC(20~30VDC)
 
48VDC(40~60VDC)
 
 
110VDC(90~130VDC)
 
220VDC(170~260VDC)
Working

While AC bypass mainly supplies electricity, DC inversion is for standby;

While DC inversion mainly supplies electricity, DC bypass is for standby; automatic switching.

Bypass input voltage(AC)
220V±20%
Bypass input frequency(Hz)
50±2.5Hz
Output
Voltage(AC)
220±2%
Frequency
50Hz±0.5%
Wave form
Sine wave
Wave distortion
THD<3% (Linear load)
Rated power
0.8 lag
Current peak coefficient
3:1, suitable for rectifying load
Transient range of dynamic voltage
0-100% load change, < ±6%
Overload capacity
While exceeding 120% rated load, the machine can alarm and close.
Efficiency
>81%
Noise(1 meter distance)
<55dB
Protection
Protection against overcurrent, protection against overloas, protection against input voltage
LED indicator light
The states of mains supply, inversion, overload and battery, etc
LCD liquid crystal display
Input/output voltage, Input/output frequency, battery voltage and load percentage
Warn
Low voltage of battery
Pulsed sound per second
Overload
Successive
Machine fault
Successive
Computer control interface
RS232 interface
Real time monitoring and controlling the working state of machine, warning of mains supply failure, warning of low woltage of battery, saving documwnts as well as closing the machine.

1. Telemeter the input/output voltage and frequency of machine, load, battery capacity which will be shown appropriately on PC machine

2. Real time telemetering the working state of machine

3. Preset the machine function of starting & closing machine through PC

4. Before battery is used up, it can automatically save documents, close PC and then close itself.

Using environment
Temperature
0-40℃
Relative humidity
30%-90% no condensation
Height above sea level
<1000m (the power will drop 1% per increase of 100m, max.:4000m)
Weight(kg)
16
19.1
30.3
33.5
83
171
220
257
287
342
Overall dimensions(mm)
Length
515
560
635
550
790
Width
180
210
270
450
580
Height
315
370
690
1000
1180

If there are any changes in specification, we wont inform you separately. In addition, order for special specification is accepted.

 